It supports the detection of the voltage and temperature of the battery cell, as well as the voltage and current of the whole group. It has SOC and SOH detection and calculation, which is easy to maintain and use, and maximizes the safety, reliability and service life of the battery;
Integrated BMS and bi-directional DCDC: 48V 100AH battery can be converted to 400V interface, support different battery mix and match, different manufacturers of inverter applications, realize full-featured intelligent management of lithium batteries;
Parallel power expansion characteristics: a maximum of 32 sets of batteries can be connected in parallel;
Alarm management: support abnormal alarms such as overvoltage, undervoltage, overcurrent, high and low temperature;
Abnormal protection: support overvoltage, undervoltage, overcurrent, short circuit, high and low temperature, battery failure, hardware failure and other abnormal protection;
Equalization function: support the real-time equalization function of the battery;
Information reporting: Provide northbound CAN/RS485 interface, upload alarm and status data through CAN/RS485 interface;
Easy to maintain and use: supports multiple activation methods, forced power-off function, maintenance mode, automatic arrangement of addresses and physical locationss;
Maintenance-free: The battery module is maintenance-free during use, saving customers' battery operation and maintenance testing costs, and reducing the frequency of site replacement.
Model | TP-BMSP400/12A1 |
Working temperature | -20℃~+60℃ (for use above 55°C, power derating requirements must be met) | |||||
Cooling method | Natural heat dissipation | |||||
Dimensions (L*W*Dmm) | 420*114*49mm | |||||
Total Weight | 3600g | |||||
Surface Coating Color | Black | |||||
Protection level | IP40 | |||||
Project | Unit | Minimum | Typical | Maximum | Remarks | |
Charging working status | Input (high voltage side) voltage range | VDC | 250 | 400 | 450 | The actual input voltage is mainly determined by PCS/inverter control; 370V-430V full power work |
Output (battery) voltage range | VDC | 36 | 50 | 58 | ||
Output power limit | W | 0 | / | 5000 | ||
Current limiting | A | 10 | 100 | 120 | Battery current | |
Efficiency | % | 98 | / | / | Rated power | |
Discharge working state | Input (charging) voltage range | VDC | 42 | 49 | 58 | |
Output (battery) voltage range | VDC | 250 | 390 | 450 | The output voltage is controlled by this product, 310V-450V full power work | |
Output limited power | W | / | 5000 | 5500 | ||
Current limiting | A | 10 | 100 | 125 | ||
Efficiency | % | 98 | / | / |
Support battery type | Lithium iron phosphate |
Rated battery voltage | DC 48V |
Support battery capacity | 48V/100Ah or 48V/200Ah |
Communication interface | RS485; CAN |
Number of strings supported | 15/16S |
Alarm and protection | Overvoltage, undervoltage, short circuit, overload, overtemperature, low temperature protection, etc. |